Skip to content

Potentiometer SCSCL Servo - Memory Table

For SCS/SCSCL half-duplex TTL series servos. Two-byte fields are transmitted with the high byte first.

1 Servo Communication Protocol

Servos use the FT-SCS proprietary protocol. The default baud rate is 1 Mbps or 500 kbps over a TTL single-wire bus, 8 data bits, no parity, 1 stop bit; configurable baud rate range 38400~1 Mbps (500 kbps), default communication address (station number) 1.

FT-SCS Protocol

2 Servo Memory Table Definition

If a function address uses two bytes of data, the high byte is at the leading address and the low byte at the following address: for example, the goal position of 288 steps (0x0120) is written as 01 20, not 20 01.

Notes:

  • Initial values and ranges vary by model (shown as – in the table); refer to the data for your model.
  • A "step" is the smallest position unit (the "minimum resolution angle" used throughout this table): the series divides the whole mechanical travel of the potentiometer (commonly 210°, 220°, 270°, 300°, depending on the model) into 1024 equal parts, one step each, so 0~1023 steps span the full travel; the angle per step = travel ÷ 1024, per your model's data.
  • Steps and pitfalls for common operations (changing the ID, the baud rate, the travel range and protection) are in "4 Common Workflows" below.

2.1 Version Information

Address (DEC) Address (HEX) Function Bytes Initial value Access Range Unit Description
0 0x00 Firmware major version 1 – R
1 0x01 Firmware minor version 1 – R
2 0x02 END 1 1 R 1 indicates the big-endian storage structure
3 0x03 Servo major version 1 – R
4 0x04 Servo minor version 1 – R

2.2 EEPROM Configuration

Address (DEC) Address (HEX) Function Bytes Initial value Access Range Unit Description
5 0x05 Servo ID 1 1 R/W 0~253 ID Unique main ID on the bus
6 0x06 Baud rate 1 0 R/W 0~7 None 0-7 correspond to baud rates: 1000000(0), 500000(1), 250000(2), 128000(3), 115200(4), 76800(5), 57600(6), 38400(7)
7 0x07 Undefined 1 – R/W –
8 0x08 Response status level 1 1 R/W 0~1 None 0: no response packet for instructions other than READ and PING; 1: response packet for all instructions
9 0x09 Minimum angle limit 2 20 R/W 0~1023 Step Set the minimum running angle limit; the value must be smaller than the maximum angle limit; minimum angle limit = maximum angle limit = 0 enters motor mode
11 0x0B Maximum angle limit 2 1003 R/W 0~1023 Step Set the maximum running angle limit; the value must be larger than the minimum angle limit; minimum angle limit = maximum angle limit = 0 enters motor mode
13 0x0D Maximum temperature limit 1 70 R/W 0~100 °C Temperature threshold of the overheat protection
14 0x0E Maximum input voltage 1 – R/W 0~254 0.1V Voltage threshold of the over-voltage protection; maximum input voltage = minimum input voltage = 0 means voltage feedback is disabled
15 0x0F Minimum input voltage 1 40 R/W 0~254 0.1V Voltage threshold of the under-voltage protection; maximum input voltage = minimum input voltage = 0 means voltage feedback is disabled
16 0x10 Maximum torque 2 1000 R/W 0~1000 0.1% Sets the upper limit of the output torque; written to address 48 (torque limit) at power-on
18 0x12 Phase 1 – R/W 0~254 None Special function byte; do not modify unless specifically required
19 0x13 Unload condition 1 – R/W 0~254 None Set bit to 1 to enable the corresponding protection, set bit to 0 to disable it; bit definitions in 3.3 Unload Condition
20 0x14 LED alarm condition 1 – R/W 0~254 None Set bit to 1 to enable the flashing LED alarm, set bit to 0 to disable the flashing LED alarm; bit definitions in 3.4 LED Alarm Condition
21 0x15 Position loop P (proportional) coefficient 1 – R/W 0~254 None Proportional coefficient of the motor
22 0x16 Position loop D (derivative) coefficient 1 – R/W 0~254 None Derivative coefficient of the motor
23 0x17 Undefined 1 – R/W – –
24 0x18 Minimum startup torque 2 – R/W 0~1000 0.1% Sets the minimum output startup torque of the servo
26 0x1A Positive deadband 1 1 R/W 0~16 Step The minimum unit is one minimum resolution angle
27 0x1B Negative deadband 1 1 R/W 0~16 Step The minimum unit is one minimum resolution angle
28~36 0x1C~0x24 Undefined 9 – R/W – –
37 0x25 Holding torque 1 20 R/W 0~254 1% Output torque after entering overload protection, e.g. 20 means 20% of the maximum torque
38 0x26 Protection time 1 200 R/W 0~254 10ms Duration for which the current load output stays above the overload torque, e.g. 200 means 2 seconds, maximum 2.54 seconds
39 0x27 Overload torque 1 80 R/W 0~254 1% Maximum torque threshold that starts the overload protection timer, e.g. 80 means 80% of the maximum torque

2.3 SRAM Control

Address (DEC) Address (HEX) Function Bytes Initial value Access Range Unit Description
40 0x28 Torque switch 1 0 R/W 0~2 None Write 0: torque output off / free state; write 1: torque output on; write 2: damping state
41 0x29 Undefined 1 – R/W – –
42 0x2A Goal position 2 0 R/W 0~1023 Step Each step is one minimum resolution angle; absolute position control; the maximum corresponds to the maximum effective angle
44 0x2C Running time 2 0 R/W 0~9999/-1000~1000 1ms/0.1% Time to move from the current position to the goal position; effective when the running speed is 0; in motor mode this parameter sets the output PWM duty cycle — write the magnitude (0~1000) and set BIT10 for reverse
46 0x2E Running speed 2 Factory default maximum speed R/W 0~1000 Step/s Number of steps moved per unit time (per second)
48 0x30 Lock flag 1 1 R/W 0~1 None Write 0 to close the write lock: values written to EEPROM addresses persist after power-off; write 1 to open the write lock: values written to EEPROM addresses do not persist
49~55 0x31~0x37 Undefined 7 – R/W – –

2.4 SRAM Feedback

Address (DEC) Address (HEX) Function Bytes Initial value Access Range Unit Description
56 0x38 Present position 2 – R – Step Current position in steps; each step is one minimum resolution angle; absolute position control, the maximum value corresponds to the maximum effective angle
58 0x3A Present speed 2 – R – Step/s Rotational speed of the motor, steps moved per unit time (per second)
60 0x3C Present load 2 – R – 0.1% Duty cycle of the output driving the motor; BIT10 is the direction bit
62 0x3E Present voltage 1 – R – 0.1V Current working voltage of the servo
63 0x3F Present temperature 1 – R – °C Current internal working temperature of the servo
64 0x40 Async write flag 1 0 R – None Flag used with the async write instruction: set to 1 as soon as the async write instruction (0x04, unicast or broadcast) is accepted, cleared to 0 as soon as the execution instruction (0x05) is accepted; a direct write (0x03) does not change it; it is a RAM bit and clears at power-off.
65 0x41 Servo status 1 0 R – None A bit set to 1 indicates the corresponding error; the bit is set as soon as the threshold is crossed, independent of the switch in 19 Unload condition
66 0x42 Moving flag 1 0 R – None 1 while the servo is moving, 0 when the target is reached and the servo stops; stays 0 when no updated goal position is written
67~77 0x43~0x4D Undefined 11 – – – – Reserved

2.5 Factory Parameters

Address (DEC) Address (HEX) Function Bytes Initial value Access Range Unit Description
78 0x4E PWM mode maximum step 1 20 R – None
79 0x4F Moving speed threshold*50 1 1 R – None
80 0x50 DTs(ms) 1 20 R – None
81 0x51 Minimum speed limit*50 1 1 R – None
82 0x52 Maximum speed limit*50 1 – R – None
83 0x53 Acceleration 1 20 R – None

3 Special Byte Explanation

3.1 Servo Phase

Bit (weight): Description

  • BIT0 (1): Drive direction phase; (0) forward, (1) reverse
  • BIT1 (2): ----
  • BIT2 (4): ----
  • BIT3 (8): Speed mode; (0) speed 0 means stop, (1) speed 0 means maximum speed — this bit decides what 46 Running speed = 0 means
  • BIT4 (16): ----
  • BIT5 (32): PWM phase, (0) in phase, (1) inverted
  • BIT6 (64): Voltage mode, (0) 1.5K low-voltage sampling, (1) 1K high-voltage sampling
  • BIT7 (128): ----

Note

If multiple bits are set at the same time, the phase value is the sum of the bit values.

3.2 Servo Status

Servo status: 0 means normal, 1 means abnormal

Bit (weight): Description

  • BIT0 (1): Voltage status
  • BIT1 (2): ----
  • BIT2 (4): Temperature status
  • BIT3 (8): ----
  • BIT4 (16): ----
  • BIT5 (32): Load status
  • BIT6 (64): ----
  • BIT7 (128): ----

Note

If multiple statuses occur at the same time, the status value is the sum of the bit values. Example: over-voltage/under-voltage together with servo overheating gives a status value of 4+1=5;

3.3 Unload Condition

Unload condition: 0 means off, 1 means on

Bit (weight): Description

  • BIT0 (1): Voltage protection
  • BIT1 (2): ----
  • BIT2 (4): Overheat protection
  • BIT3 (8): ----
  • BIT4 (16): ----
  • BIT5 (32): Load overload
  • BIT6 (64): ----
  • BIT7 (128): ----

Note

If multiple bits are set at the same time, the unload condition value is the sum of the bit values. Example: with voltage protection and overheat protection enabled together, the unload condition value is 4+1=5;

3.4 LED Alarm Condition

LED alarm condition: 0 means off, 1 means on

Bit (weight): Description

  • BIT0 (1): Voltage alarm
  • BIT1 (2): ----
  • BIT2 (4): Overheat alarm
  • BIT3 (8): ----
  • BIT4 (16): ----
  • BIT5 (32): Load overload alarm
  • BIT6 (64): ----
  • BIT7 (128): ----

Note

If multiple bits are set at the same time, the LED alarm condition value is the sum of the bit values. Example: with the voltage alarm and the overheat alarm enabled together, the alarm condition value is 4+1=5;

Do not reuse addresses across families

Other application layers may use the same address with a different meaning. Return to Bus Protocol and select the matching memory table.

4 Common Workflows

Once the connection is up, day-to-day work on the servo comes down to reading and writing a handful of registers. This section collects the common ones by task; how to build the instruction frames is out of scope here — see FT-SCS Protocol. All numbers below refer to the addresses in this table.

4.0 Before You Start

  • EEPROM area (2.2, 5~39): write 48 Lock flag = 0 before changing anything, and write 1 back afterwards, otherwise the value is not saved. Measured: with the lock flag at 1 a write is still accepted and takes effect immediately, but it does not survive power-off; enabling (40 Torque switch) does not affect saving.
  • SRAM area (2.3, 40~55): write directly, effective immediately, lost at power-off — good for trial writes; 48 Lock flag itself lives here, so writing it needs no unlock.
  • 56~66 in 2.4 and 78~83 in 2.5 are read-only; reading them does not change the servo state.

4.1 Getting the Servo Moving

Goal: turn the output shaft through a small angle for the first time.

Step Action Register Value / example
1 Read the present position, call it P 56 Present position read-only, e.g. 500 steps
2 Drop the maximum torque to 30% 16 Maximum torque 300 (factory 1000)
3 Set the running speed 46 Running speed 200 (200 steps/s)
4 Turn the torque output on (can be skipped) 40 Torque switch 1
5 Write the goal position 42 Goal position P + 50 (move 50 steps only)

Turning by angle

The angle per step is set by the mechanical travel of your model and is not a fixed number: angle per step = travel ÷ 1024.

Desired result How to work it out Worked example (270° model)
Turn another 90° from the present position (recommended) read 56 Present position as P, goal = P ± (90° ÷ angle per step) P ± 341
Turn 90° from the start of the travel goal = 90° ÷ angle per step 341
  • Steps = angle ÷ angle per step = angle × 1024 ÷ travel; e.g. 60° is about 228 steps on a 270° model.
  • If you do not know your travel: open SC series specifications, go to your model page and read the "Rotation angle" line.
  • Try P + 341 first (that is 90° on a 270° travel; for other travels, use 90° ÷ the angle per step of your model and round): if it turns the wrong way, use P − 341. Which side adds depends on how the potentiometer and the horn are mounted.
  • 0 steps is one end of the potentiometer travel (the other end is 1023); to confirm, write 42 Goal position = 0 (it is clamped to 20 by 9 Minimum angle limit) and watch which side the shaft stops on.
  • The goal must stay within 9 Minimum angle limit / 11 Maximum angle limit (see 4.2).

Speed conversion

Direction Formula Example
Value written → speed RPM = 46 Running speed × travel ÷ 6144 270° model, 200 written → 8.8 RPM
Target speed → value 46 Running speed = RPM × 6144 ÷ travel 30 RPM → 683 on a 270° model
  • 6144 = 1024 × 6: the 1024 is the divisor above (the travel split into steps), the 6 comes from 1 RPM = 6°/s; RPM is used here only as an angular-velocity unit — the travel is less than a full turn, so the servo never actually revolves.
  • At 200 steps/s, 90° (341 steps on a 270° model) takes about 1.7 s.

Notes:

Check: while moving, 66 Moving flag is 1 and returns to 0 on arrival; 56 Present position should then equal the goal (the boundary value if clamped by the travel range).

4.2 Setting the Travel Range

Goal: limit how far the output shaft may turn.

Registers: 9 Minimum angle limit and 11 Maximum angle limit, in steps; both are in the EEPROM area, so unlock 48 Lock flag before writing.

Steps:

  • Convert the boundaries you want into steps (one step = travel ÷ 1024, see "Turning by angle" in 4.1).
  • Write 9 and 11; 9 must be smaller than 11; write 48 Lock flag = 0 first and set it back to 1 afterwards.

Notes:

  • Minimum angle limit = maximum angle limit = 0 enters motor mode (the shaft rotates continuously), which is an advanced use; to return to normal mode, write both limits again.
  • The limits only constrain goal position commands; an external force can still push the shaft past them.

Check: first set 11 Maximum angle limit to 500 (EEPROM, so unlock first), then write 42 Goal position = 600; the shaft should stop at 500 steps and go no further.

4.3 Changing the ID

Goal: change the bus address of the servo; do this before building a multi-servo bus.

Registers: 5 Servo ID, 48 Lock flag.

Pitfalls:

  • Only write it when this is the only servo on the bus; with several servos, power them one at a time.
  • Writing through the broadcast address changes every servo on the bus at once.
  • ID range 0~253; never duplicate an ID on the same bus.
  • After a successful write the servo answers on the new ID at once and no longer answers on the old one; the re-lock and any PING afterwards must use the new ID in the ID byte (no need to reopen the port) — sending with the old ID only times out.

Steps: confirm this is the only servo on the bus → write 48 = 0 → write 5 = new ID → using the new ID write 48 = 1.

Check: a PING with the new ID (or a read of 5) should answer, and the old ID should not. For the broadcast method see FT-SCS Protocol.

4.4 Changing the Baud Rate

Goal: change the communication baud rate to match the host.

Registers: 6 Baud rate, 48 Lock flag.

Pitfalls:

  • What you write is the gear number 0~7, not the baud rate itself (0=1000000, 1=500000, 2=250000 … full mapping in row 6 of the 2.2 table).
  • The current connection drops the moment the write succeeds: the servo switches to the new gear at once and stops answering on the old rate, so reconnect at the new rate (change the rate and reopen the port in your serial tool, or reinitialise the UART on the host) before sending anything else — the re-lock included; with a wrong gear you can only retry gear by gear or restore the factory default.
  • The host and every servo on the bus must use the same gear; a mixed bus does not communicate.

Steps: unlock as described in 4.0 Before You Start → write 6 = new gear (the connection drops here) → reconnect at the new rate → write 48 = 1.

Check: reconnect at the new rate and send a PING; an answer is all you need. For lost connections see Troubleshooting.

4.5 Configuring Protection

Goal: set temperature, voltage and overload protection so a stall does not damage the servo.

Registers:

Role Register Notes
Temperature threshold 13 Maximum temperature limit crossing it sets the matching status bit in 65
Voltage threshold 14 Maximum input voltage / 15 Minimum input voltage 0.1 V; 15 defaults to 40, i.e. 4.0 V; voltage feedback is off only when both are 0
Whether to unload the output 19 Unload condition bit-wise enable of each protection, bit definitions in 3.3 Unload Condition
Whether to flash the LED 20 LED alarm condition a separate channel; it flashes only on models with an LED, bit definitions in 3.4 LED Alarm Condition
Overload torque drop 37 Holding torque / 38 Protection time / 39 Overload torque once the load exceeds the torque in 39 (80 = 80%) for the time in 38 (200 = 2 s), the output torque drops to the holding torque in 37 (20 = 20%)

All of the above are in the EEPROM area (2.2), so unlock 48 Lock flag before writing.

Key points:

  • Temperature and voltage protection need both conditions to fire: the matching bit of 19 Unload condition set to 1 (that item enabled) plus the measured value crossing the threshold in 13~15 → that protection acts (unloads the output); with the bit at 0 it never acts.
  • Overload is a separate chain: once the load exceeds 39 Overload torque for 38 Protection time, the output torque drops to 37 Holding torque; whether the output is also unloaded is decided by BIT5 (load overload) of 19.
  • 65 Servo status reflects the detection layer: the bit is set as soon as the threshold is crossed, whether or not 19 is enabled; 20 LED alarm condition is another independent channel — an alarm on 20 never substitutes for unloading on 19.
  • 13~15 are thresholds, not switches: writing 0 to one of them does not disable that protection.

Check: confirm the matching bit of 19 is set to 1, then cross a threshold on purpose (or stall the servo) and read 65: the matching bit turns 1 and the output follows the protection; both return to 0 once the condition clears.

4.6 Reading Status to Troubleshoot

Goal: locate a problem with read-only registers when the servo misbehaves.

Registers: 56 Present position, 58 Present speed, 60 Present load, 62 Present voltage, 63 Present temperature, 65 Servo status, 66 Moving flag; all read-only, reading them at will does not affect the servo.

Order to check:

  • Read 65 Servo status: if it is not 0, decode it bit by bit with 3.2 Servo Status (e.g. 1 = voltage, 4 = temperature).
  • Read 62 Present voltage / 63 Present temperature: check that the supply voltage and the internal temperature are normal.
  • Read 60 Present load: mask BIT10 (direction bit) first, then scale 0~1000; a value close to 100% for a long time means a stall or too little torque.
  • Read 56 / 58 / 66: check that the position feedback and the motion state match the command.

Source Definition